Daikin Heat Pump: Capacitor voltage check (Check No.21)

Updated · by Aurora Star Tech Inc.

Capacitor voltage check (Check No.21) on a Daikin heat pump: Checks that the main capacitor voltage is safe before working on the outdoor unit.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Outdoor unit DC capacitor

How to fix capacitor voltage check (check no.21): step by step

  1. Turn the circuit breaker off and wait 10 minutes.
  2. 09/12 class: measure the voltage between DC_P2 (+) and DC_N2 (-). It must be 50 V or less.
  3. 18/24 class: measure the voltage between FU2 and DC-. It must be 50 V or less.
  4. The test points may be coated. Make firm contact with the multimeter probes.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin Inverter Pair FTXM-W/V service manual, p. 156. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.