Daikin Heat Pump: Brazing refrigerant piping with nitrogen

Updated · by Aurora Star Tech Inc.

Brazing refrigerant piping with nitrogen on a Daikin heat pump: Braze with nitrogen flowing through the pipe so oxide scale does not form inside the lines. Without it, scale can clog or damage valves and compressors.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Heat source unit and cascade unit refrigerant piping

How to fix brazing refrigerant piping with nitrogen: step by step

  1. Replace the air with nitrogen and keep nitrogen flowing while brazing.
  2. Use a pressure reducing valve on the nitrogen supply. Set it to about 3 psi (0.02 MPa).
  3. Protect the area around the joint with tape or a pad.
  4. Do not use antioxidant paste when brazing; residue can clog piping and damage parts.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Heat Pump codes

Source: Daikin Mega-Q installation manual, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.