Daikin Heat Pump: Auxiliary output wiring
Auxiliary output wiring on a Daikin heat pump: The thermostat Aux outputs are dry contacts that close to switch on an auxiliary device. A 24VAC control signal must be routed through one of the Aux contacts. Aux terminals are chosen in the Daikin One installer wizard. Use a minimum of 18-gauge wire and keep the run under 125 feet.
Applies to: Auxiliary equipment on the One Touch thermostat
How to fix auxiliary output wiring: step by step
- Wire the auxiliary device through an Aux 1 or Aux 2 dry contact (N.O. and Com).
- Route the 24VAC control signal through one of the Aux contacts.
- Use at least 18-gauge wire, no longer than 125 feet.
- Select the Aux terminal in the Daikin One installer wizard.
- Confirm the field device has its own line voltage supply through the relay.
If the unit shows an error code, look it up: Daikin Heat Pump codes
Source: Daikin One Touch installation guide, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.