Daikin General: Wiring the thermostat to the translation adaptor

Updated · by Aurora Star Tech Inc.

Wiring the thermostat to the translation adaptor on a Daikin general: Wire the thermostat to the adaptor with the correct gauge and length, and verify voltage at each stage.

Homeowner with a heating or cooling system problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Daikin One+ Smart Thermostat

Common causes of wiring the thermostat to the translation adaptor

  • Wiring run too long
  • Wrong wire gauge or conductor count
  • Power wires reversed
  • Incorrect wiring

How to fix wiring the thermostat to the translation adaptor: step by step

  1. Use four-conductor 18 AWG field wire, no longer than 125 ft.
  2. Check voltage before wiring: about 0.6 VDC between Data 1 and 2, and 24 VDC between R and C.
  3. Wire R, C, Data Line 1 and Data Line 2, plus 24 V power and 24 V common, as shown.
  4. Check voltage again after wiring.
  5. If the PWR LED flashes green, the power wires are reversed; correct them.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin General codes

Source: Daikin One+ installation & commissioning (S21), p. 15. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.