Daikin General: Overcool setting and how it changes thermostat cycling
Overcool setting and how it changes thermostat cycling on a Daikin general: Overcool 0 cycles the system at the displayed cooling set point. Overcool 2 makes the thermostat run past the displayed set point using an internal over-set point that the user does not see. The thermo on/off deadband is fixed at ±1°F for mini-split and multi-split indoor units.
Applies to: Daikin One+ thermostat, mini-split and multi-split indoor units
If the unit shows an error code, look it up: Daikin General codes
Source: Daikin One+ Installation & Commissioning (S21), p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.