Daikin General: Installing the heater accessory on the ventilator
Installing the heater accessory on the ventilator on a Daikin general: Mounting and wiring the heater to the ventilator cabinet. Disconnect power before starting.
Applies to: DQ-P-70-AH-H heater with Daikin One Powered Ventilator
How to fix installing the heater accessory on the ventilator: step by step
- Switch off the main disconnect and lock or tag it.
- Remove the four screws holding the outlet duct collar and gasket on the ventilator, and set them aside.
- Fit the duct collar and gasket onto the heater end panel using those screws.
- Remove the two screws holding the ventilator control compartment cover and set them aside.
- Punch out the electrical knockout on the ventilator front with a straight-blade screwdriver.
- Remove and discard the foam insert behind the knockout.
- Fit the plastic bushing, run the heater harness through it and the knockout, and connect it to the 3-pin connector on the LCD controller.
- Secure the heater to the ventilator with the six screws: two per side and two on the bottom.
- Refit the control compartment cover with its two screws.
If the unit shows an error code, look it up: Daikin General codes
Source: IO-DPVH installation and operation manual, p. 3. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.