Daikin Air Handler: Two-piece unit external static (cased coil with gas furnace or modular blower)
Two-piece unit external static (cased coil with gas furnace or modular blower) on a Daikin air handler: Used when an EEV cased coil is paired with a gas furnace or modular blower. Clean filters must be installed. Readings are taken at the furnace or modular blower.
Applies to: EEV cased coil with gas furnace or modular blower
Common causes of two-piece unit external static (cased coil with gas furnace or modular blower)
- Closed dampers or registers
- Undersized or oversized ductwork
- Dirty filter or electronic air cleaner restriction
How to fix two-piece unit external static (cased coil with gas furnace or modular blower): step by step
- With clean filters installed, measure return static at the inlet of the gas furnace or modular blower. This is negative.
- If a filter is installed with the furnace, measure between the filter and the furnace.
- Measure supply static at the outlet of the furnace or modular blower. This is positive.
- Add the two readings for total external static. Include any electronic air cleaner in the reading.
- Use the furnace or modular blower airflow chart to find CFM.
- If total static is outside the allowed range, check dampers, registers and duct layout.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.