Daikin Air Handler: S-4 Checking transformer and control circuit
S-4 Checking transformer and control circuit on a Daikin air handler: Each indoor unit has a step-down transformer (208/230 or 115 V primary to 24 V secondary). The outdoor sections have no transformer.
Applies to: Daikin EEV air handlers and cased coils
Common causes of s-4 checking transformer and control circuit
- No secondary voltage can mean a faulty transformer, bad wiring or bad splices
- Transformer inoperative if primary voltage is present but secondary is not
How to fix s-4 checking transformer and control circuit: step by step
- Disconnect all power before servicing.
- Remove the control panel cover to access the transformer.
- With power on, check voltage across the transformer secondary (R to C) with a voltmeter.
- If there is no voltage, check transformer primary voltage at the incoming line connections or splices.
- If line voltage is present at the primary and wiring and splices are good, replace the transformer.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin SiUS612209EB service instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.