Daikin Air Handler: Running the UltraCheck-EZ ECM diagnostic tool
Running the UltraCheck-EZ ECM diagnostic tool on a Daikin air handler: The tool sends a run signal to the ECM motor and shows communication status. Use the indication table to decide whether to replace the control or the motor.
Applies to: Emerson UltraCheck ECM motors
Common causes of running the ultracheck-ez ecm diagnostic tool
- Tool fuse open or tool not on 24 VAC
- Motor control/end bell fault
- Motor winding fault
How to fix running the ultracheck-ez ecm diagnostic tool: step by step
- Disconnect power to the indoor unit.
- Disconnect the 4-circuit control harness from the motor.
- Plug the 4-circuit connector from the tool into the motor control connector.
- Clip one alligator clip to a ground source and the other to a 24 VAC source. The clips are not polarized.
- Do not connect the tool to any source other than 24 VAC, as this blows its non-replaceable fuse.
- Turn on power to the indoor unit.
- Press the orange power button to start the motor, and allow up to 5 seconds to start.
- Read the green LED and motor action against the indication table.
- Press the orange power button to stop the motor, disconnect power and the tool.
- Reconnect the 4-wire harness from the control board to the motor.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.