Daikin Air Handler: Reading the state, error and airflow on the 2-digit display
Reading the state, error and airflow on the 2-digit display on a Daikin air handler: With the indoor unit powered, the 2-digit display cycles through the current state, any error code and the estimated airflow. The EEV cased coil does not show airflow. During a minor error in defrost or emergency mode the display shows the state with the error.
Applies to: EEV indoor units with 2-digit 7-segment display. The EEV cased coil does not indicate airflow.
How to fix reading the state, error and airflow on the 2-digit display: step by step
- Read the state shown first (for example FC, FH, dF, or EE).
- If an error code is present in standby or normal mode, the display keeps showing it. Look it up in the indoor error code table.
- To read airflow, watch for the "A" indicator, then the upper two digits and the lower two digits of CFM shown in turn. Example: 1240 CFM shows "A", "12", then "40".
- During a minor error in defrost, the display shows dF, then the error code, then airflow.
- During a minor error in emergency mode, the display shows EE, then the error code.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 26-27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.