Daikin Air Handler: Read the last six faults (fault recall)
Read the last six faults (fault recall) on a Daikin air handler: The control board has a push button that shows the last six faults on the 2-digit display. The control must be in standby (no thermostat inputs) first.
Applies to: EEV indoor units with 2-digit display and FAULT RECALL button
How to fix read the last six faults (fault recall): step by step
- Make sure the control is in standby with no thermostat inputs.
- Press and hold FAULT RECALL for 2 to 5 seconds. The display shows solid "--".
- Release the button. The display shows the most recent fault.
- Press FAULT RECALL again to step back through older faults.
- After the last fault the display shows "--" and the control returns to standby.
- Repeated identical faults show at most three times.
- If the button is left alone for more than 3 minutes, the control returns to standby.
- Holding the button longer than 15 seconds also returns the control to standby.
If the unit shows an error code, look it up: Daikin Air Handler codes
More service & test modes tips for air handler
Source: SiUS612209EA service instructions, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.