Daikin Air Handler: Navigating the EEV indoor unit mode display for error history
Navigating the EEV indoor unit mode display for error history on a Daikin air handler: The 2-digit display is a backup to the thermostat for reading the six most recent EEV indoor faults and for erasing the history. Navigation depends on how long the FAULT RECALL button is held and released. The flowchart on the source page is partly unclear, so verify each press with the display.
Applies to: EEV indoor units
How to fix navigating the eev indoor unit mode display for error history: step by step
- Start from screen zero (no display, standby).
- Hold FAULT RECALL for more than 2 seconds, then release between 2 and 5 seconds. The first (most recent) error code appears flashing.
- Press FAULT RECALL to step to the next error code. Repeat to reach the last code.
- Hold FAULT RECALL for more than 5 seconds to reach the erase step. The display shows a solid "88" for 3 seconds before all diagnostic codes are erased.
- If the display is idle for 3 minutes, the unit returns to screen zero.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 28-29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.