Daikin Air Handler: Measuring air handler external static
Measuring air handler external static on a Daikin air handler: Total external static is the absolute sum of the return (negative) and supply (positive) static readings. Example: -0.30 inH2O + 0.20 inH2O = 0.50 inH2O (-74.7 Pa + 49.8 Pa = 124.5 Pa).
Applies to: Air handler external static pressure
Common causes of measuring air handler external static
- Restriction in return or supply duct
- Dirty filter
How to fix measuring air handler external static: step by step
- Using a draft gauge (inclined manometer), measure return static at the unit inlet. This is negative.
- If a filter is installed, measure between the filter and the air handler.
- Measure supply static in the supply duct. This is positive.
- Add the two readings to get total external static. Both can be read at once on the manometer.
- Use the airflow table to find CFM at the measured static.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.