Daikin Air Handler: Measure two-piece unit external static (S-203A)
Measure two-piece unit external static (S-203A) on a Daikin air handler: A two-piece unit is an EEV cased coil with a gas furnace or modular blower. External static is measured at the furnace or modular blower.
Applies to: EEV cased coil with gas furnace or modular blower
Common causes of measure two-piece unit external static (s-203a)
- Restricted return or supply duct
- Closed dampers or registers
- Dirty filter or electronic air cleaner loading
How to fix measure two-piece unit external static (s-203a): step by step
- With clean filters in the indoor unit, measure return static at the inlet of the gas furnace or modular blower (negative pressure).
- If a filter is in the return, measure between the filter and the furnace or blower.
- Measure supply static at the outlet of the gas furnace or modular blower (positive pressure).
- Add the two absolute readings for total external static. Include any electronic air cleaner in the readings.
- Use the airflow chart for the gas furnace or modular blower to find CFM at the measured static.
- If total static is outside the minimum or maximum, check for closed dampers, registers, and undersized or oversized poorly laid out ductwork.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin SiUS612209EA service instructions, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.