Daikin Air Handler: Measure air handler external static (S-203)
Measure air handler external static (S-203) on a Daikin air handler: External static is the sum of the absolute values of the return and supply static readings.
Applies to: DV**FEC / DFVE** air handlers
Common causes of measure air handler external static (s-203)
- Restricted return or supply duct
- Dirty filter
How to fix measure air handler external static (s-203): step by step
- With a draft gauge (inclined manometer), measure return duct static at the unit inlet (negative pressure). If a filter is installed, measure between the filter and the air handler.
- Measure supply duct static (positive pressure).
- Add the two absolute readings for total external static. Example: -0.30 inH2O + 0.20 inH2O = 0.50 inH2O (-74.7 Pa + 49.8 Pa = 124.5 Pa).
- Use the airflow table for the air handler to find CFM at that total external static.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin SiUS612209EA service instructions, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.