Daikin Air Handler: Heating emergency mode – EEV air handler electric heat
Heating emergency mode - EEV air handler electric heat on a Daikin air handler: Runs the electric heat strips with no thermostat, in High or Low heat level. The cycle timing is in the sequence entry for this mode. Outdoor unit must stay stopped during this mode.
Applies to: DFVE EEV air handler with electric heater kit
How to fix heating emergency mode - eev air handler electric heat: step by step
- Set DS-3 S-9 to S-12 to match the installed heater kit size using the heater kit table.
- On the indoor control board DS-6, set S-21 and S-22 for the heat level: S-21 OFF and S-22 ON for High heat level; S-21 ON and S-22 ON for Low heat level. Default is both OFF.
- If the control board shows an Ed error on startup, the DS-3 heater kit DIP settings do not match the kit. Correct them to clear the error.
- Once communication is re-established, set DS-6 S-21 and S-22 back to OFF (normal operation).
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin SiUS612209EA service instructions, p. 33. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.