Daikin Air Handler: ECM motor test with UltraCheck-EZ tool
ECM motor test with UltraCheck-EZ tool on a Daikin air handler: The UltraCheck-EZ diagnostic tool runs the ECM motor to show whether the motor and control/end bell are working. Its fuse is not replaceable and the tool must only be connected to 24 VAC.
Applies to: Emerson ECM blower in indoor air handler
Common causes of ecm motor test with ultracheck-ez tool
- Motor control/end bell fault
- Motor fault
- Tool not getting 24 VAC
How to fix ecm motor test with ultracheck-ez tool: step by step
- Disconnect power to the indoor unit.
- Unplug the 4-circuit control harness from the motor.
- Plug the 4-circuit connector from the tool into the motor control connector.
- Connect one alligator clip to a ground source and the other to a 24 VAC source (clips are not polarized).
- Turn power on to the indoor unit.
- Press the orange power button to send a run signal. Allow up to 5 seconds for the motor to start.
- If the orange button does not light, the tool fuse is open or the tool is not on 24 VAC.
- Read the green LED and the motor action. Blinking LED with rotating motor means the motor and control/end bell are good. LED off with rotating motor means replace the control/end bell. Blinking LED with motor not rotating means check the motor. LED off with motor not rotating means replace the control/end bell and verify the motor.
- Press the orange button to stop the motor, disconnect power and the tool, then reconnect the 4-wire harness.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin SiUS612209EA service instructions, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.