Daikin Air Handler: ECM high voltage power circuit checks
ECM high voltage power circuit checks on a Daikin air handler: Checks the line voltage feed to the ECM motor from the 5-circuit power connector.
Applies to: ECM blower in indoor air handler
Common causes of ecm high voltage power circuit checks
- No supply voltage to indoor unit
- Open wiring in the 5-circuit power harness
How to fix ecm high voltage power circuit checks: step by step
- Disconnect power to the indoor unit.
- Unplug the 5-circuit power connector to the ECM motor.
- Turn power on to the indoor unit.
- Measure voltage between pins 4 and 5. It should equal the indoor unit supply voltage.
- Measure voltage between pins 4 and 3, then between pins 5 and 3. Each should be about half the reading from step 4.
- If no voltage is present, check supply voltage to the indoor unit (see S-1).
- Disconnect power, then reconnect the 5-circuit harness.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin SiUS612209EA service instructions, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.