Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Daikin Air Handler: ECM high voltage power circuit check

Updated · by Aurora Star Tech Inc.

ECM high voltage power circuit check on a Daikin air handler: Checks the line voltage feed to the ECM motor power connector with the 5-circuit harness unplugged.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECM motor 5-circuit power connector

Common causes of ecm high voltage power circuit check

  • No supply voltage to the indoor unit
  • Open harness or connector

How to fix ecm high voltage power circuit check: step by step

  1. Disconnect power to the indoor unit.
  2. Unplug the 5-circuit power connector at the ECM motor.
  3. Turn on power to the indoor unit.
  4. Measure voltage between pins 4 and 5. It should equal the indoor unit supply voltage.
  5. Measure voltage between pins 4 and 3. It should be about half the step 4 voltage.
  6. Measure voltage between pins 5 and 3. It should be about half the step 4 voltage.
  7. If no voltage is present, check supply voltage to the indoor unit.
  8. Disconnect power, then reconnect the 5-circuit harness.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Air Handler codes

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 18. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Air Handler Emergency

647-657-2977