Updated · by Aurora Star Tech Inc.

ECM control/end bell check on a Daikin air handler: Use this when the ECM motor control is suspected. The control/end bell has an NTC thermistor and large capacitors.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECM motor control/end bell

Common causes of ecm control/end bell check

  • Cracked NTC thermistor
  • Bulging or swollen capacitors
  • Low insulation resistance at the 3-circuit connector

How to fix ecm control/end bell check: step by step

  1. Disconnect power and wait 5 minutes for the motor capacitors to discharge.
  2. Disconnect the motor control and motor power harnesses.
  3. Remove the blower assembly from the indoor unit.
  4. Remove the three screws holding the control/end bell to the motor and disconnect the 3-circuit harness.
  5. Inspect the NTC thermistor. Replace the control/end bell if it is cracked or broken.
  6. Inspect the large capacitors. Replace the control/end bell if any are bulging or swollen.
  7. With an ohmmeter, check resistance between each terminal of the 3-circuit connector. 1 MΩ or greater is good. Replace the control/end bell if below 1 MΩ.
  8. Reassemble in reverse order and reinstall the blower assembly.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Air Handler codes

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 19. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.