Daikin Air Handler: Cooling emergency mode – EEV air handler
Cooling emergency mode - EEV air handler on a Daikin air handler: The indoor unit provides airflow on its own and the outdoor unit runs at a set cooling level. Both units run independently in this mode.
Applies to: DFVE EEV air handler with DX6VS/DZ6VS outdoor unit
How to fix cooling emergency mode - eev air handler: step by step
- Select the airflow on the indoor unit with DS-4 S-13 and S-14 (25 percent, 50 percent, 75 percent or 100 percent).
- On indoor DS-6, set S-21 to ON and S-22 to OFF to enable emergency indoor fan operation.
- Select the cooling level on the outdoor unit DS-2 (Low, Medium or High). See the DS-2 table.
- When communication is restored, return all these switches to default settings.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin SiUS612209EA service instructions, p. 34. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.