Daikin Air Handler: Check external static pressure on a two-piece indoor unit

Updated · by Aurora Star Tech Inc.

Check external static pressure on a two-piece indoor unit on a Daikin air handler: Used for an EEV cased coil paired with a gas furnace or modular blower. Total external static is the sum of the return and supply readings. Use it to find the airflow (CFM) from the furnace or blower chart.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Two-piece EEV cased coil with gas furnace or modular blower

Common causes of check external static pressure on a two-piece indoor unit

  • Closed dampers or registers
  • Undersized or oversized or poorly laid out ductwork
  • Dirty or restrictive filter, or an electronic air cleaner adding restriction

How to fix check external static pressure on a two-piece indoor unit: step by step

  1. Start with clean filters in the indoor unit.
  2. Measure return static at the inlet of the gas furnace or modular blower with an inclined manometer or Magnehelic gauge. The reading is negative (example -0.30 inH2O / -74.7 Pa).
  3. If a filter is installed with the furnace, measure between the filter and the furnace instead.
  4. Measure supply static at the outlet of the gas furnace or modular blower. The reading is positive (example 0.20 inH2O / 49.8 Pa).
  5. Add the absolute values of the two readings to get total external static (example 0.50 inH2O / 124.5 Pa). Both can be read at once on the manometer.
  6. Include any electronic air cleaner in the reading if one is installed.
  7. Look up the airflow (CFM) for that static on the furnace or modular blower chart.
  8. If total static is above the allowed maximum or below the minimum, check for closed dampers, registers and duct layout.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Air Handler codes

Source: SiUS612209EA service instructions, p. 24. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.