Daikin Air Handler: Blower not running: EEM motor air handler
Blower not running: EEM motor air handler on a Daikin air handler: Quick check for an EEM (constant torque) blower motor that will not run.
Applies to: Air handlers used with DC3S/DC4S/DC5S and DH4S/DH5S units
How to fix blower not running: eem motor air handler: step by step
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- Check for 240 V on motor terminals L and N. No voltage: check breaker, fuses and wiring.
- Check for 24 V between C and the tap terminal in use. No voltage: make sure the thermostat is calling for fan and check the low voltage fuse and wiring.
- With both voltages present and the motor not running, replace the motor or module.
If the unit shows an error code, look it up: Daikin Air Handler codes
Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Troubleshooting chart Air Handler - EEM Motor p.46; Checking High Efficiency Motors p.26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.