Daikin Air Conditioner: Testing the run capacitor
Testing the run capacitor on a Daikin air conditioner: Three ways to check a run capacitor.
Applies to: DC3SQN, DC4SQA, DC4SEA, DC5SEA (single stage R-32 condensing units with CoreSense module)
How to fix testing the run capacitor: step by step
- Kill power at the disconnect before working in the unit. There can be more than one power source.
- Discharge the capacitor through a 200-300 ohm resistor before handling.
- Ohm test: set the meter to at least 1k ohm, touch the terminals. A good cap shows a reading for a moment then goes back to OL. No change = dead.
- Capacitance test: take it out of the circuit, read it in capacitance mode. Close to the printed value (may read a bit low) = good. Much lower or nothing = replace.
- Under load: read the amps on the wire from HERM to the compressor start terminal, multiply by 2,652, divide by the voltage between HERM and C. Compare the result to the printed MFD and its tolerance.
If the unit shows an error code, look it up: Daikin Air Conditioner codes
Models
DC3SQN**10AADC4SEA**10AADC4SQA**10AADC5SEA**10AA
Source: Daikin RSD6200301 Service and Troubleshooting, DC3S/DC4S/DC5S AC and DH4S/DH5S heat pump R-32 (07-2024), Checking Capacitor p.23-24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.