Daikin Air Conditioner: Remove heat exchanger – AC models, 3.5 to 5.0 ton
Remove heat exchanger - AC models, 3.5 to 5.0 ton on a Daikin air conditioner: Heat exchanger and partition plate removal on AC-only outdoor units.
Applies to: 3.5 to 5.0 ton AC outdoor units
How to fix remove heat exchanger - ac models, 3.5 to 5.0 ton: step by step
- Remove the 3 screws holding the rear cover and remove the cover.
- Heat the brazed joints of the heat exchanger and disconnect them. Protect nearby plastic and putty as noted in the manual.
- Remove the 2 screws holding the heat exchanger and lift it out.
- Remove the partition plate. On 4-screw models remove 4 screws; on 3-screw models remove 3 screws.
- On reassembly, insert the hook on the bottom frame into the slit in the partition plate.
If the unit shows an error code, look it up: Daikin Air Conditioner codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 126-127. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.