Applies to: 3.5 to 5.0 ton AC outdoor units

How to fix remove compressor - ac models, 3.5 to 5.0 ton: step by step

  1. Remove the 6 screws holding the stop valve mounting plate and set the plate aside. Use the same screws when reassembling (marked M5 x 16, 3-class hex head tapping screws). If a conduit tube is attached to the plate, remove it first.
  2. Remove the top sound blanket, then the body sound blanket.
  3. Remove the terminal cover.
  4. Disconnect the compressor lead wires. Wire colours are U red, V yellow, W blue. The wiring differs by model, so connect the leads exactly as shown in the manual on reassembly.
  5. Remove the overload (OL) device. When refitting, hook the lower tabs of the retainer into the fixture's square holes first, then push the upper hooks until they latch.
  6. Heat the brazed compressor piping joints and disconnect them. Protect nearby parts with a sheet or steel plate.
  7. Remove the 2 nuts that secure the compressor.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Daikin Air Conditioner codes

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 121-123. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.