Daikin Air Conditioner: Disconnect outdoor wiring on AC units (1.5 to 3.0 ton)
Disconnect outdoor wiring on AC units (1.5 to 3.0 ton) on a Daikin air conditioner: Removal sequence for outdoor wiring, thermistors and pipe sensors on 1.5 to 3.0 ton cooling-only models.
Applies to: DX6VS / DZ6VS AC outdoor units, 1.5 to 3.0 ton
How to fix disconnect outdoor wiring on ac units (1.5 to 3.0 ton): step by step
- Cut the 4 clamps and disconnect the PS lead wire at connector X840A. On reassembly, fix the lead to the same position with new clamps.
- Remove the 3 clamps and disconnect the compressor lead wire at the U, V, W connector.
- Remove the outdoor air thermistor and outdoor coil thermistor. On reassembly, route the lead wires so they do not touch sharp edges.
- Remove the suction pipe, discharge pipe and liquid pipe thermistors. Detach the OL (overload protector) relay connector and the HPS connectors. Cut the 2 clamps and remove the insulation tube.
- On reassembly, position the slit of the insulation tube opposite the suction pipe thermistor.
If the unit shows an error code, look it up: Daikin Air Conditioner codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 91-92. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.