Daikin Air Conditioner: Check capacitor DC voltage before servicing (1.5 to 5.0 ton outdoor units)
Check capacitor DC voltage before servicing (1.5 to 5.0 ton outdoor units) on a Daikin air conditioner: Confirm the capacitor is discharged before touching it. The voltage between the C+ and C- terminals must read 50 V DC or less. Page text for the procedure steps is partly garbled in this copy, so verify against the full manual before work.
Applies to: 1.5 to 3.0 ton and 3.5 to 5.0 ton outdoor units
How to fix check capacitor dc voltage before servicing (1.5 to 5.0 ton outdoor units): step by step
- Turn off power to the unit and wait about 10 minutes.
- Set a multimeter to the DC voltage range.
- Measure across C+ and C- on the capacitor.
- Proceed only if the reading is 50 V DC or less. Otherwise, discharge the capacitor as the manual directs before continuing.
If the unit shows an error code, look it up: Daikin Air Conditioner codes
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 5-6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.