Carrier Mini-Split: Wall hole slope for drainage
Wall hole slope for drainage on a Carrier mini-split: The wall hole must drain toward the outside so condensate does not run back into the room.
Applies to: D5FSHA sizes 6K to 36K
How to fix wall hole slope for drainage: step by step
- Drill the wall hole with a 2.5 in (65 mm) or 3.54 in (90 mm) core drill.
- Drill at a slight downward angle so the outdoor end is about 0.2-0.275 in (5-7 mm) lower than the indoor end.
- Place the protective wall cuff in the hole.
If the unit shows an error code, look it up: Carrier Mini-Split codes
More commissioning tips for mini-split
Source: D5FSHA installation manual, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.