Carrier Mini-Split: Removing refrigerant and evacuating before opening the circuit
Removing refrigerant and evacuating before opening the circuit on a Carrier mini-split: Follow this order when breaking into the refrigerant circuit.
Applies to: Repairs that open the refrigerant circuit
How to fix removing refrigerant and evacuating before opening the circuit: step by step
- Remove refrigerant safely following local and national rules.
- Evacuate the system.
- Purge the circuit with oxygen-free nitrogen. Purging is optional for A2L.
- Evacuate again. This step is optional for A2L.
- When using flame to open the circuit, keep flushing with inert gas.
- Do not use compressed air or oxygen to purge.
- Break vacuum with oxygen-free nitrogen, fill to working pressure, vent to atmosphere, then pull down again. Repeat until no refrigerant is left.
- Vent to atmospheric pressure before work on the system.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
45MBCAQ12XA3D5FLCAH36XAKD5FLCAH48XAKD5FSCAH12XAKD5FSCAH18XAKD5FSCAH24XAK
Source: D5FSCAH / D5FLCAH service manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.