Carrier Mini-Split: Refrigerant leak shutdown – multi-zone

Updated · by Aurora Star Tech Inc.

Refrigerant leak shutdown - multi-zone on a Carrier mini-split: The outdoor unit shuts off, the emergency shutoff valve closes, all EEVs close, and all indoor units run at turbo fan speed. The unit detecting the leak shows EHC1 or EHC2. Other indoor units show ECC1.

Homeowner with a ductless mini-split problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Multi-zone systems

How to fix refrigerant leak shutdown - multi-zone: step by step

  1. Once the leak drops below the LFL threshold, the audible alarm resets after 2 minutes and error codes clear after 5 minutes.
  2. The shutoff valve opens automatically after 2.5 hours.
  3. To bypass the valve time lock, press and hold the point check button on the MZU for 10 seconds, only if no leak is detected.
  4. Power cycling the MZU does not reset the time lock.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Carrier Mini-Split codes

Models

D5FSFAH09XAKD5FSFAH12XAKD5FSFAH16XAK

Source: Carrier D5FSFAH service manual, p. 16. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.