Carrier Mini-Split: Refrigerant leak detected by sensor
Refrigerant leak detected by sensor on a Carrier mini-split: When the leak sensor detects refrigerant, the indoor unit shows an error code and buzzes, the outdoor compressor stops immediately, and the indoor fan keeps running.
Applies to: Units with refrigerant leak sensor, R454B flammable refrigerant
Common causes of refrigerant leak detected by sensor
- Refrigerant leak in the refrigerant circuit or at field joints
How to fix refrigerant leak detected by sensor: step by step
- Remove or extinguish all open flames and ignition sources.
- Ventilate the area and keep any mechanical ventilation openings clear.
- Locate the leak with an approved electronic detector (1/8 oz/5 g per year sensitivity) or a bubble/fluorescent leak detection fluid. Do not use a halide torch or naked flame.
- If brazing is needed, recover all refrigerant first or isolate that section with shut-off valves.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Source: Carrier D5FSHA installation manual, p. 5-6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.