Carrier Mini-Split: Recovering and decommissioning a flammable refrigerant system
Recovering and decommissioning a flammable refrigerant system on a Carrier mini-split: Only competent, certified technicians should decommission. Oil and refrigerant samples should be taken first if reuse may be needed.
Applies to: Decommissioning R454B equipment
How to fix recovering and decommissioning a flammable refrigerant system: step by step
- Make sure electrical power is available and isolate the system electrically.
- Take oil and refrigerant samples before recovery if analysis may be needed.
- Pump down the system if possible. If not, fit a manifold to recover from several points.
- Keep the recovery cylinder on scales and do not fill it above 80% liquid volume.
- Do not exceed the cylinder maximum working pressure.
- Remove the cylinders and equipment promptly and close all isolation valves.
- Do not charge recovered refrigerant into another system unless it has been cleaned and checked.
- Label the equipment as decommissioned and emptied, dated and signed, and show that it contains flammable refrigerant.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
45MBCAQ12XA3D5FLCAH36XAKD5FLCAH48XAKD5FSCAH12XAKD5FSCAH18XAKD5FSCAH24XAK
Source: D5FSCAH / D5FLCAH service manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.