Carrier Mini-Split: Pressure and vacuum test of field piping
Pressure and vacuum test of field piping on a Carrier mini-split: Test field piping after install and before charging. The tightness test for indoor joints uses a sensitivity of 5 g/year.
Applies to: Field-made refrigerant piping
How to fix pressure and vacuum test of field piping: step by step
- Pressure test field piping with inert gas. Use the low side design pressure for the low side and the high side design pressure for the high side. If the sides cannot be isolated, test the whole system to the low side design pressure.
- Hold the test pressure for at least 1 hour with no drop on the gauge. Gauge resolution must not exceed 5% of test pressure.
- Evacuate the system. Isolate from the pump and confirm the pressure does not rise above 1500 microns within 10 minutes.
- Use the vacuum level in the manual, which is the lower of 500 microns or the local code value.
- Test indoor field joints with a method of 5 g/year sensitivity or better at no less than 0.25 times the maximum allowable pressure. No leak is allowed.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
45MBCAQ12XA3D5FLCAH36XAKD5FLCAH48XAKD5FSCAH12XAKD5FSCAH18XAKD5FSCAH24XAK
Source: D5FSCAH / D5FLCAH service manual, p. 6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.