Carrier Mini-Split: Power supply, wiring and protection requirements
Power supply, wiring and protection requirements on a Carrier mini-split: Fixed wiring needs an all-pole disconnect and a residual current device. Use only the specified wire and dedicated circuit.
Applies to: D5FSOAH indoor and outdoor units
How to fix power supply, wiring and protection requirements: step by step
- Use only the specified wire. If the wire is damaged, have it replaced by the manufacturer, its service agent or a similarly qualified person.
- Ground the product at installation.
- Use an all-pole disconnect with at least 3 mm contact clearance on all poles, in the fixed wiring.
- Use a residual current device rated at no more than 30 mA where leakage current may exceed 10 mA.
- Use a dedicated circuit and breaker. Do not share the outlet. Do not use defective or under-rated breakers.
- Do not modify or extend the power cable.
- Wire all connections to the Electrical Connection Diagram on the indoor and outdoor unit panels.
- Route wiring so the control board cover closes fully, and clamp cables so the terminals are not stressed.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FSOAH06XAKD5FSOAH12XAKD5FSOAH18XAK
More other tips for mini-split
Source: Carrier D5FSOAH service manual, p. 2, p. 4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.