Carrier Mini-Split: Power and communication wiring between indoor and outdoor units
Power and communication wiring between indoor and outdoor units on a Carrier mini-split: Power and communication run from the outdoor unit to the indoor unit as four conductors. The wiring is polarity sensitive.
Applies to: Indoor and outdoor unit field wiring
How to fix power and communication wiring between indoor and outdoor units: step by step
- Use 14/3 stranded wire with ground, 600 V rated, for the outdoor-to-indoor run.
- Do not use BX cable.
- Keep polarity correct on all connections.
- In a high EMF area with communication faults, use 14/2 stranded shielded wire for L2 and S; land the shield to ground at the outdoor unit only.
- Size all wire per NEC/CEC and local code using the MCA and MOP values.
- Tighten every terminal; loose connections can overheat.
- Keep wires away from refrigerant tubing, the compressor and moving parts.
- Provide a disconnect within sight of and readily accessible from the unit.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
D5FSOAH06XAKD5FSOAH12XAKD5FSOAH18XAK
Source: D5FSOA Product Data, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.