Carrier Mini-Split: Outside air output (CN8)
Outside air output (CN8) on a Carrier mini-split: Output for energising an outside air fan through a relay.
Applies to: D5FSCAH / D5FLCAH indoor unit
How to fix outside air output (cn8): step by step
- Output is 208/230 VAC. Do not exceed 1 A (200 W).
- Power is on when the indoor fan runs and off when the indoor fan stops.
- No power on CN8 during force cooling or capacity test mode.
- Use a separate power supply for the outside air fan. CN8 should only drive a relay coil.
If the unit shows an error code, look it up: Carrier Mini-Split codes
More other tips for mini-split
Source: Carrier D5FSCAH/D5FLCAH service manual, p. 13. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.