Carrier Mini-Split: Opening the refrigerant circuit and recharging (flammable refrigerant R-454B)
Opening the refrigerant circuit and recharging (flammable refrigerant R-454B) on a Carrier mini-split: Only trained and certified technicians may open the refrigerant circuit. Make sure the area is ventilated and there are no ignition sources before working.
Applies to: D5FSHAH systems using R-454B
How to fix opening the refrigerant circuit and recharging (flammable refrigerant r-454b): step by step
- Recover the refrigerant into the correct recovery cylinders.
- Evacuate the system.
- Purge the circuit with oxygen-free nitrogen, then evacuate again.
- Use nitrogen flushing if you cut open the circuit with a flame.
- Open the circuit.
- Do not use compressed air or oxygen to purge.
- Use only suitable tools and keep charging hoses as short as possible.
- Ground the refrigeration system before charging.
- Charge by the liquid method and take care not to overfill.
- Pressure test with oxygen-free nitrogen before recharging.
- Leak test after charging and before commissioning, then leak test again before leaving the site.
- Label the system when charging is complete.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Models
Source: Carrier D5FSHAH Owner's Manual, p. 4. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.