Carrier Mini-Split: Leak checking a system with flammable refrigerant
Leak checking a system with flammable refrigerant on a Carrier mini-split: Find refrigerant leaks without any ignition source on a flammable refrigerant system.
Applies to: D5FSCAH / D5FLCAH
How to fix leak checking a system with flammable refrigerant: step by step
- Never use a halide torch or any open-flame detector.
- Use an electronic leak detector rated for the refrigerant. Calibrate it in a refrigerant-free area and confirm it is set to no more than 25% of the LFL.
- Use leak detection fluids for a bubble or fluorescent check. Do not use chlorine-based detergents.
- If a leak is suspected, remove or put out all open flames first.
- If the leak needs brazing, recover the refrigerant or isolate that part of the system with shut-off valves before working on it.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Source: Carrier D5FSCAH/D5FLCAH service manual, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.