Carrier Mini-Split: Install the indoor drain line
Install the indoor drain line on a Carrier mini-split: Set up the drain so water runs away from the unit and cannot flow back. In HEAT mode the outdoor unit also discharges water, so keep the hose where it will not cause damage or a slip hazard.
Applies to: Indoor unit drainage, 6K-18K
How to fix install the indoor drain line: step by step
- Connect the drain pipe to the indoor unit with the drain adapter.
- Slope the drain pipe downward at least 1/100 along its whole length.
- Hang supports every 39-59 in (1-1.5 m) so the pipe does not sag.
- If the drain outlet is higher than the pump joint, add a lift pipe no higher than 29.5 in (75 cm) from the ceiling board and less than 11.8 in (30 cm) from the unit.
- Keep the hose level or tilted up no more than 3 in (75 mm) to avoid air bubbles.
- Insulate all drain piping to prevent condensation.
- Use a metal clamp or protection tube on extended drain pipe so it cannot pull loose.
- Do not pull the drain pipe hard. Bent or badly installed pipe can cause a water level switch fault.
- Run the outlet to a safe spot, at least 1.9 in (50 mm) above ground. If discharging to a sewer, use a U or S trap.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Source: D5FSOAH installation instructions, p. 17-18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.