Carrier Mini-Split: Buried refrigerant piping limits
Buried refrigerant piping limits on a Carrier mini-split: Buried line length is limited to prevent refrigerant migrating to a cold buried section and causing slugging at start-up.
Applies to: Refrigerant piping
Common causes of buried refrigerant piping limits
- Refrigerant migrates to cooler buried pipe during shutdown
How to fix buried refrigerant piping limits: step by step
- Do not bury more than 36 in. (914 mm) of refrigerant pipe.
- If any section is buried, provide a 6 in. (152 mm) vertical rise to the outdoor unit valve connections.
If the unit shows an error code, look it up: Carrier Mini-Split codes
Source: Carrier D5FSOAH installation manual, p. 2. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.