Carrier Air Conditioner: Delay before the compressor restarts
Delay before the compressor restarts on a Carrier air conditioner: The outdoor unit waits before starting again - usually normal.
Applies to: Carrier Infinity 19VS variable speed air conditioner 24VNA9
Common causes of delay before the compressor restarts
- Pressure equalizer valve cycle after every compressor stop
- 10-minute warm-up after high voltage power-up
- Protection delays from fault codes
How to fix delay before the compressor restarts: step by step
- After every compressor stop the pressure equalizer valve opens for 150 s, then 15 s off before the next start - this cannot be bypassed.
- After power-up the compressor sump warms for 10 minutes (code 68).
- Brown-out recovery delay can be skipped by briefly shorting the Forced Defrost pins.
- Check the STATUS light for any other fault delay.
If the unit shows an error code, look it up: Carrier Air Conditioner codes
Models
Carrier 2-stage 24ANB/25HNB
24ANB12424ANB13624ANB14824ANB16024ANB72424ANB73624ANB74824ANB760
Carrier Infinity 19VS 24VNA9
24VNA924VNA91324VNA92424VNA92524VNA93624VNA93724VNA94824VNA94924VNA960
Source: Carrier 25VNA8 / 24VNA9 Service Manual, Timing / delays p.8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.