Carrier Air Conditioner: Decommissioning and refrigerant recovery
Decommissioning and refrigerant recovery on a Carrier air conditioner: Safe recovery steps before decommissioning a flammable refrigerant system.
Applies to: Decommissioning flammable refrigerant equipment
How to fix decommissioning and refrigerant recovery: step by step
- Confirm the technician knows the equipment fully.
- Take an oil and refrigerant sample if analysis may be needed before reuse.
- Make sure electrical power is available, then isolate the system electrically.
- Pump the system down if possible; otherwise make a manifold to recover from several points.
- Place the recovery cylinder on scales before recovery.
- Keep the recovery process supervised at all times.
- Do not fill cylinders above 80% liquid volume.
- Do not exceed the cylinder maximum working pressure.
- Remove filled cylinders and equipment from site promptly and close isolation valves.
- Do not charge recovered refrigerant into another system unless cleaned and checked.
- Label the equipment as decommissioned and emptied, with date and signature.
- Label the equipment as containing flammable refrigerant.
If the unit shows an error code, look it up: Carrier Air Conditioner codes
Source: Carrier D5FUHA installation instructions, p. 8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.