Carrier Air Conditioner: Checking room area against refrigerant charge
Checking room area against refrigerant charge on a Carrier air conditioner: Room area limits for an A2L/R454B system serving a room or ducted rooms.
Applies to: R454B charge limits and room sizing
How to fix checking room area against refrigerant charge: step by step
- Measure room area A from the floor projection of walls, partitions and doors.
- Do not count spaces joined only by drop ceilings, ductwork or similar connections as one room.
- Keep the air duct outlet in the room at 7.2 ft (2.2 m) or higher from the floor.
- Compare actual charge Mc with the allowable maximum charge for the room area (Table 6).
- For connected rooms, check total conditioned area TA against TAmin.
- Make sure the room the unit is in is at least 20% of TAmin.
- Provide openings per Table 6 and the opening conditions, with 50% of Anvmin below 200 mm from the floor.
If the unit shows an error code, look it up: Carrier Air Conditioner codes
Source: Carrier D5FUHA installation instructions, p. 10-12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.