Carlin Boiler: Setting Carlin EZ combustion (inside air or ducted air)
Setting Carlin EZ combustion (inside air or ducted air) on a Carlin boiler: Target numbers depend on the incoming air temperature when the air is piped from outside.
Applies to: Carlin EZ burners on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers
Common causes of setting carlin ez combustion (inside air or ducted air)
- CO2 drifts when the cover goes on or outside air temperature changes
How to fix setting carlin ez combustion (inside air or ducted air): step by step
- Run the burner at least 15 minutes, with the cover on if it has one, before final readings.
- Smoke must be zero. Set draft per the boiler (natural draft usually -0.01 to -0.02 in. w.c. over fire).
- Inside air: aim for 12.0-12.5% CO2 (3.9-4.6% O2).
- Ducted air, measure the incoming air temperature: -20 to 0°F = 10.2-11.0% CO2; 5 to 30°F = 11.0-11.5%; 35 to 60°F = 11.5-12.2%; 65°F and up = 12.0-12.5%.
- Open the air band to lower CO2, close it to raise CO2. Tighten the clamp screw.
- Check the flame does not hit any surface. Recheck the install after 1-2 weeks of running.
Source: Carlin Model EZ 1,2,3 and LF Oil/Biofuel Burners Instruction Manual MNEZ123 (with Weil-McLain WGO/WTGO/SGO supplement MN97410E-B100), Adjustment and verification, Table 5, p.15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.