Carlin Boiler: Moving a Carlin EZ burner to high biodiesel blends (above B20 / B100)
Moving a Carlin EZ burner to high biodiesel blends (above B20 / B100) on a Carlin boiler: Biodiesel cleans sludge out of the tank at first and lowers CO2. Set up before the fuel changes.
Applies to: Carlin EZ burners on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers
Common causes of moving a carlin ez burner to high biodiesel blends (above b20 / b100)
- Sludge loosened from the tank plugging the filter or sticking the pump
- Low CO2 after the switch
- Older burner not converted for high blends
How to fix moving a carlin ez burner to high biodiesel blends (above b20 / b100): step by step
- Use a single-pipe system and a 10 micron spin-on filter (NORA recommendation). Change filters more often during the switch.
- Before going above B20, set CO2 at the high end (not below 11.5%). For WGO/WTGO/SGO going to B100 the supplement says set 12.25-12.5% CO2 on #2 oil first.
- Older Carlin burners need the field conversion (new head, higher pump pressure, B100 pump, other control settings) from Carlin's online OEM guide before running high blends.
- Use the B100 column settings in the boiler's burner table for nozzle, pump pressure, head bar and air band.
Source: Carlin Model EZ 1,2,3 and LF Oil/Biofuel Burners Instruction Manual MNEZ123 (with Weil-McLain WGO/WTGO/SGO supplement MN97410E-B100), Biodiesel best practices, p.20; supplement table 1 note, p.1. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.