Carlin Boiler: Checking the Carlin EZ ignitor
Checking the Carlin EZ ignitor on a Carlin boiler: Safe way to test the ignitor.
Applies to: Carlin EZ burners on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers
Common causes of checking the carlin ez ignitor
- Weak or no spark
How to fix checking the carlin ez ignitor: step by step
- Never short the high voltage clips with a screwdriver.
- 40700 and 40900 ignitors: only check by watching for spark at the electrodes with the oil supply OFF.
- 45000 ignitor: power off, open the ignitor plate fully, set the high voltage clips to a 1/2 to 3/4 in. gap. Power on briefly. Spark jumping the gap = ignitor is good.
- Also check electrode gap and insulators per the electrode settings in the manual (p.10-11).
Source: Carlin Model EZ 1,2,3 and LF Oil/Biofuel Burners Instruction Manual MNEZ123 (with Weil-McLain WGO/WTGO/SGO supplement MN97410E-B100), Maintenance procedures - Checking ignitor, p.17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.