Carlin Boiler: Carlin EZ with CAP system shuts down or locks out (blocked air intake)
Carlin EZ with CAP system shuts down or locks out (blocked air intake) on a Carlin boiler: The CAP system stops the burner when the outside combustion air pipe is blocked.
Applies to: Carlin EZ burners on Weil-McLain WGO, WTGO, SGO and Ultra Oil boilers
Common causes of carlin ez with cap system shuts down or locks out (blocked air intake)
- Snow, ice or a bird nest blocking the intake termination
- Intake pipe too long (over 80 ft total, each elbow counts 10 ft) or wrong pipe
- Missing bird screen / wrong termination
How to fix carlin ez with cap system shuts down or locks out (blocked air intake): step by step
- The control checks the intake during pre-purge. Blocked = it will not try to light.
- If the intake blocks while running, the burner shuts off after 20 seconds of blockage.
- After a shutdown it recycles up to 3 times with a 1 minute wait. Still blocked on all 3 = lockout for that call for heat.
- Clear the termination. It should be a downward PVC elbow with the bird screen, at least 12 in. above expected snow.
- Intake pipe must be schedule 40 or 80 PVC, 3 in., max 80 ft total with each elbow counted as 10 ft.
- Reset the primary control per its data sheet and watch a full cycle.
Source: Carlin Model EZ 1,2,3 and LF Oil/Biofuel Burners Instruction Manual MNEZ123 (with Weil-McLain WGO/WTGO/SGO supplement MN97410E-B100), Optional combustion air intake systems - CAP System, p.6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.