Beckett Boiler: Setting CF375 combustion with instruments
Setting CF375 combustion with instruments on a Beckett boiler: Use an analyzer, not your eyes. Run the burner 5-10 minutes first.
Applies to: Beckett CF375
Common causes of setting cf375 combustion with instruments
- Wrong air setting
- Wrong draft
- Biodiesel blend reading off on the analyzer
How to fix setting cf375 combustion with instruments: step by step
- Set over-fire draft to the boiler maker's number (natural draft is usually -0.01 to -0.02 in. w.c.).
- Adjust the air until you get a trace of smoke. Note the CO2 (or O2) there.
- Add air to drop CO2 by 1.5 to 2 points (O2 goes up about 2.0 to 2.7 points). Example from the manual: 13.5% to 11.5% CO2.
- Smoke should now be zero. If draft changed, recheck smoke and CO2.
- Tighten the air band, shutter and head plate screws. If the burner has a cover, recheck with the cover on.
- Biodiesel: set the analyzer to light / #2 oil. On B100 the CO2 reads about 0.3% low, so add 0.3%. Easier: use O2, aim for 4.5-5.7% O2 (about 11.3-12.3% CO2).
- Start and stop several times and test the primary control and all safety controls.
If the unit shows an error code, look it up: Beckett Boiler codes
Source: Beckett CF375 Burner Manual (Weil-McLain WGO/WTGO/SGO sizes 8-9, 0125), Set combustion with instruments, p.14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.