Beckett Boiler: Priming the CF375 oil pump (air in the oil line)

Updated · by Aurora Star Tech Inc.

Priming the CF375 oil pump (air in the oil line) on a Beckett boiler: How to bleed the fuel unit on the CF375 with the GeniSys 7565 control.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Beckett CF375 with GeniSys 7565 control

Common causes of priming the cf375 oil pump (air in the oil line)

  • Air in the supply line after a run-out, filter change or new install

How to fix priming the cf375 oil pump (air in the oil line): step by step

  1. Never let oil spray into a hot chamber while bleeding. Put a gauge on the nozzle port line or open the bleed valve fully so oil does not collect in the chamber.
  2. Do not start the burner if the chamber is flooded with oil, full of vapour or very hot. Flooded = power and oil off, clean out the oil first.
  3. Open the oil valves, close the air band and crack the air shutter (starting point only).
  4. Call for heat. Open the bleed fitting into a container until all bubbles and froth are gone, then close it.
  5. For a long purge: while the igniter is still on, tap the ACTION button. Pump Prime mode runs motor, igniter and valve for 4 minutes with the SYS light solid yellow, then SYS goes green and the control returns to standby.
  6. Other way per the manual: after the burner starts, hold ACTION about 15 seconds until SYS turns yellow, then let go.
  7. Set pump pressure to the boiler maker's value (factory nozzle port setting is 140 psig or more).
  8. Do not try to relight with the burner running if the flame goes out during start-up.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Beckett Boiler codes

Source: Beckett CF375 Burner Manual (Weil-McLain WGO/WTGO/SGO sizes 8-9, 0125), Start up burner/set combustion, p.13. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.